4-Terminal Earth Resistance Tester and Soil Resistivity Tester
DY4300B is a 2/ 3/ 4-Wire Digital Earth Resistance/ Earth Resistivity Tester equipped with a microcomputer and can measure earth resistances and calculate earth resistivities (ρ). The instrument can measure earth resistances on power distribution lines, in-house wiring system and electrical appliances etc. due to the low output voltage: approx 10Vrms or less.
·Designed to meet following safety standards.
IEC 61010-1 (CAT. III 300V, CAT. IV 150V, Pollution degree 2)
IEC 61010-031(Requirements for hand-held Probes)
IEC 61557-1, 5 (Earth Resistance Tester)
· Stable measurement results can be obtained under a noisy environment by introducing the FFT (Fast Fourier Transform) technology.
Dot-matrix 192x64, Monochrome LCD.
Backlight function to view the test results in dimly areas.
Can switch frequencies of measuring signal4-kind of frequencies : 94 / 105 / 111 / 128Hz, are selectable by hand or automatically.
Rk Function is available to cancel the residual resistance on the Test Leads.
Battery Check Function
Can measure Series Interference Voltage/ Frequency Voltage values and frequencies are displayed when Series Interference voltage (AC) exist.
Auxiliary Earth Resistance Measurement Function.
Auxiliary earth resistances are measured and displayed.
· Warning for Auxiliary Earth Resistance Measurements Warnings are displayed on the LCD when auxiliary earth resistances are too high and may result in inaccurate measurements.
·Auto-Power-Off Function.
The instrument is automatically powered off when 5 min passes without any Key operation.
·Memory Function. Can save 800 measured results.
4-Terminal Earth Resistance Tester and Soil Resistivity Tester
Applicable Standards
IEC 61010-1 Measurement CAT. III 300V, CAT. IV 150V Pollution degree 2
IEC 61010-031 Standard for hand-held Probes
IEC 61557-1, 5 Earth Resistance Tester
IEC 61326-1 EMC Standard
Measuring range and accuracy (23℃5℃,relative humidity 45~75%RH)
Function | Range | Resolution | Measuring Range | Accuracy |
Earth Resistance Re(Rg at ρ measurement) | 2Ω | 0.001Ω | 0.05~2.099Ω | ±3%rdg±0.05W |
20Ω | 0.01Ω | 0.05~20.99Ω | ±3%rdg±5rdg |
200Ω | 0.1Ω | 0.5~209.9Ω |
2000Ω | 1Ω | 5~2099Ω |
20kΩ | 10Ω | 50~20.99KΩ |
200kΩ | 100Ω | 500~209.9KΩ |
Auxiliary Earth Resistance Rh, Rs |
|
|
| 8% of Re+Rh+Rs |
Earth Resistivity ρ | 2Ω | 0.1Ωm~1Ωm Auto ranging | 0.3~395.6Ωm | ρ=2 x II x a x Rg |
20Ω | 0.3~3956Ωm |
200Ω | 0.3~39.56kΩm |
2000Ω | 0.3~395.6kΩm |
20kΩ | 0.3~1999kΩm |
200kΩ |
Series Interference Voltage Ust(A.C only) | 50V | 0.1V | 0~50.9Vrms | ±2%rdg.±2dgt (50~60Hz) |
Frequency Fst | Auto-ranging | 0.5Hz | 40Hz~500Hz |
|
· LCD Dot-matrix 192X64, monochrome Backlight.
· Earth resistance: max 209.9kW. Earth resistivity Interference Voltage: max 50.9V.
· Low Battery Warning: Battery mark appears.
· Continuous Measurement: 400 times or more with manganese batteries; repeating measurements at every 30 sec with a load of 1W at 2W range.
· Over-range Indication :OL
· Auto-Power-Off: automatically powered off when 5 min passes without any Key operation.
· Location for use: Indoor/ Outdoor use (Not completely waterproof), altitude 2000m or less.
· Applicable range: Testing earth resistance on power distribution lines, in-house wiring system and electrical appliances.
· Temperature & Humidity range (guaranteed accuracy) :23℃~5℃ , relative humidity 85% or less (no condensation)
· Operating Temperature & Humidity range :-10℃ ~ 50℃ , relative humidity75% or less (no condensation).
* Supplied Test leads cannot be used at 0℃ or less.
· Storage Temperature & Humidity range:-20℃~-60℃ , relative humidity 75% or less (no condensation).
· Overload Protection : between E-S(P) and between E-H(C) terminals AC280V / 10 sec
· Withstand Voltage : between the electrical circuit and enclosure. AC3540V(50/60Hz) / 5 sec
· Insulation Resistance : between the electrical circuit and enclosure 50MW or more / DC1000V.
· Dimension:167*185*89mm.
· Weight:900g(including batteries)
· Power source:DC12v:size AA manganese dry battery((R6P)*8
** In a use of this instrument under low temperature below 0℃, a use of alkaline batteries with low temperature spec is recommended.
Range to keep the maximum operating error
Measurement range within which the maximum operating error(±30%)applies.
2W Range:0.5W~2.099W
20gRange:2W~20.99W
200W Range:20W~209.9W
2000W Range:2kW~20.99kW
20kW Range:2kW~20.99kW
200kW Range:20kW~209.9kW
Variation of Supply Voltage : until the Battery Warning mark appears
Temperature Variation : -10℃ ~ 50℃
Series Interference Voltage: 16ˉ2/3Hz, 50Hz, 60Hz, 400Hz and DC3V.